Product manual
SPECIFICATION
product name: | Temperature and humidity transmitter |
Model: | BTH- 10A |
version: | V1.0 |
Creator: | He Genwen |
reviewed by: | Yuan Chao |
1、Product Introduction
This product BTH 10A is an industrial grade temperature and humidity transmitter with an integrated design of sensing and transmission. It is equipped with a dedicated temperature compensation circuit and linearization processing circuit, and outputs a standard current signal of 4-20mA; It has the characteristics of wide range, high accuracy, small size, easy installation, strong anti-interference ability, and good consistency.
Suitable for temperature and humidity measurement in communication rooms, factories, clean workshops, hospitals, archives, museums, warehouses, tobacco, pharmaceutical factories, HVAC, building automation, and other places。
2、Technical Parameter
Working power supply | DC24V±10% |
output signal | 4~20mA,two-wire |
Temperature measurement range | -40℃~60℃ |
Humidity measurement range | 0%RH ~100%RH |
Temperature measurement accuracy | ±1℃(@0℃~50℃) |
Humidity measurement accuracy | ±5%RH(@25℃, 30%RH~80%RH) |
response time | <15S (25℃) |
operation temperature | -40℃~60℃ |
storage temperature | -40℃~60℃ |
Installation method | hanging |
housing | ABS white 110*70*39mm |
Product weight | 85 can |
3、Appearance dimensions (unit: mm)
4、Wiring diagram
Figure 1 Physical terminal wiring diagram
Figure 2 Two wire 4-20mA wiring diagram
5、note
1. When the transmitter is connected to the controller, it is recommended to use 18-24AWG shielded cables to prevent noise interference;
2. Before connecting the power supply, it is necessary to confirm that the analog input terminal of the controller matches the output terminal of the transmitter;
3. Do not install the transmitter when the temperature exceeds the working range;
4. The transmitter should be installed in a location that can effectively reflect the temperature of the measured area, and attention should be paid to keeping it away from heat or cold sources;
5. Construction personnel should wear anti-static gloves and cut off the power supply during installation and wiring, and should not operate with electricity;
6. If there is a significant temperature difference between the installation surface and the tested environment, it is recommended to use a bracket with a distance of 20CM for installation;
6、quality assurance
Within 12 months of the product leaving the factory, free repair services will be provided based on normal use and non-human damage.